When can the LDV fleet charge?

The aggregate charger representation can use registered RAMP-mobility simulations to limit when pooled LDV chargers can operate. Builds replay the selected profile and retain annual charged-electricity output and vehicle activity. Explicit charger archetypes require annual operation. See the infrastructure method and registered RAMP inputs.

What the inherited simulations represent

Assumption: composition is embedded in the simulated shape

US NHTS and Ontario TTS selections encode different travel evidence. The registered Ontario BEV simulation also embeds vehicle/range composition, driver activities and charger assumptions. Those choices are frozen in the external output. Applying new EPA OMEGA range weights to that shape would double-count composition.

Coverage limit: calendar, travel behavior and regional transfer

The inherited reference uses Toronto time/DST and the 2018 calendar. The Ontario TTS survey input represents weekdays, and the full-year simulation repeats that travel evidence on weekends. Occupation proportions distinguish workers, students and inactive people. They leave driving status unobserved. Ontario BEV charging is a proxy for future periods, other regions and the PHEVs and motorcycles served by the same chargers.

Native normalization and utilization scaling

Current ingestion converts the registered minute-resolution power series to hourly means and retains native energy/peak checks. Let \(\boldsymbol{f_h}\) be a dimensionless normalized hourly shape, \(\boldsymbol{\bar f}\) its mean across the complete native 8,760-hour year, and \(\boldsymbol{u}\) the reviewed annual charger utilization. The emitted profile is

\[f'_h=f_h\frac{u}{\bar f},\qquad \frac1{8760}\sum_hf'_h=u.\]

Modeler note: hourly ceilings and annual utilization

The native shape is retained; the amplitude changes. Values outside the physical capacity-factor bounds fail validation. The hourly values are ceilings, accompanied by an annual utilization floor \(0.98u\) when profiles are enabled. At current \(u=0.20\), that floor is 0.196. Without a profile, annual utilization equals 0.20. This \(\boldsymbol{u}\) is not the PHEV distance utility factor used in consumption calculations.

A representative week before and after annual utilization rescaling

Figure charging-profile-1. The same registered week is shown before and after rescaling for both inherited travel simulations. Every hourly value is multiplied by \(0.20/\bar f\), computed from the complete 8,760-hour year. Titles report the actual full-year means and multiplier. Timing, daily peaks and relative variation are preserved; the illustrated week's mean need not equal 20%. The dashed line marks the annual target, rather than a flat hourly charging requirement.

The read-only LDV charging notebook calls the production hourly transformation and rescaling functions on verified registered source bytes. The same notebook compares the six registered survey/strategy runs below. It performs no source acquisition, simulation, or production writes.

How travel and charging rules shape aggregate hourly behavior

The six registered simulations combine two travel surveys with uncontrolled, night-preferred and day-preferred charging. They share a 2,499-driver simulated fleet, random seed 42 and the complete 2018 Toronto calendar. Within each survey, the strategies reuse identical mobility and active-driver evidence. Their charging differences therefore describe how parking preferences, battery state of charge and charging access act on that fixed travel realization.

Charging intensity by local hour across the six registered survey and strategy runs

Figure ldv-charge-4. Each cell is one run and Toronto local hour, averaged across the complete year and divided by that run's own annual mean charging power. A value of one equals the run's average hour; warmer cells identify hours with more charging relative to that average. Both occurrences of a repeated autumn clock hour contribute. This comparison exposes timing without equating annual energy totals or applying a new utilization target.

Uncontrolled charging follows parking opportunities after travel. Night and day strategies prefer 22:00–07:00 and 07:00–18:00 respectively; low battery state of charge can trigger emergency charging outside those windows. The resulting shape is an aggregate fleet signal. It does not identify charger occupancy, individual access constraints, or separate schedules for each charger type.

Mean hourly charging, battery mobility and active drivers for each survey and strategy

Figure ldv-charge-2. Each panel represents a survey/strategy year; each point is a mean by Toronto local hour. Grid charging power, battery-side mobility power and the active-driver count are each divided by their own full-year mean, allowing their timing to be compared despite different physical units. Active drivers measure driving, not charging vehicles or occupied chargers. The normalization preserves each signal's departure from its annual mean; it neither reconciles grid and battery energy nor establishes a causal delay between driving and charging.

These two comparisons qualify the hourly input used by the production rescaling in Figure charging-profile-1. Annual utilization determines the magnitude of the emitted capacity-factor profile; inherited travel and charging rules determine when that capacity is available. Survey differences also include different realized travel demand. The TTS weekday-data proxy, regional transfer and embedded fleet assumptions therefore remain limitations of the shape after its annual mean has been matched.

Representative time can change the annual mean

The supported mapping assigns every elapsed hour to exactly one model slice and averages its hourly factors. The builder verifies that the assigned hours match the declared slice weights and that the annual integral is preserved. A different selection or weighting of representative days can change the weighted mean:

\[\bar f_{rep}=\frac{\sum_s\omega_sf'_s}{\sum_s\omega_s}.\]

Integration limit: final time weights require their own check

Check \(\bar f_{rep}\) with the final CANOE-main weights. If it differs from \(u\), rescale against those weights and verify the resulting ceilings and utilization floor. The receiving model must couple time-resolved electricity supply to annual vehicle activity through charging. Allocating annual service uniformly across hours would impose a different charging requirement.

The profile assumptions record the source qualifications and the remaining limits on regional and weekend behavior.